[pagetitleshort]
Model: | FDK-CC600E/H2 |
Prime Power: | 540KW/675KVA |
Standby Power: | 600KW/750KVA |
60Hz/1800rpm/ThreePhase | |
Engine: | Cummins QSK19-G3 |
Alternator: | Stamford HCI544E |
[pagetitleshort]
Model: | FDK-CC600E/H2 |
Prime Power: | 540KW/675KVA |
Standby Power: | 600KW/750KVA |
60Hz/1800rpm/ThreePhase | |
Engine: | Cummins QSK19-G3 |
Alternator: | Stamford HCI544E |
Model: | FDK-CC600E/H2 |
Prime Power: | 540KW/675KVA |
Standby Power: | 600KW/750KVA |
60Hz/1800rpm/ThreePhase |
Engine Model | QSK19-G3 |
Engine Manufacturer | Cummins (CHINA CCEC) |
Cylinder quantity | 6 |
Cylinder Arrangement | In-line |
Cycle | 4 |
Aspiration | Turbo-charge |
Bore x Stroke (mm x mm) | 159×159 |
Displacement | 19L |
Compression Ratio | 15:1 |
Prime power / Speed (KW/RPM) | 608/1800 |
Standby power/ Speed (KW/RPM) | 669/1800 |
Type Injection System | Cummins MCRS |
Piston Speed | 9.5m/s |
Friction Energy Output | 59kw |
Total Lubrication System Capacity (L) | 84.4 |
Coolant Capacity (L) | 41.6 |
Fuel Consumption at 100% load (g/KWh) | 217 at 1800 rpm |
Starter motor | 24V |
Alternator | 24V |
Low idle | 700-900 rpm |
Alternator model | HCI544E |
Alternator manufacturer | STAMFORD |
Exciter type | Single bearing, Brushless, Self-excited |
Rated output prime power | 681 KVA |
Rated speed | 1800 rpm |
Rated frequency | 60Hz |
Number of phase | 3 |
Rated voltage | 440V (Available with custom requirements) |
Power factor | 0.8 |
Voltage regulation NL-FL | ≤±1% |
Insulation grade | H |
Protection grade | IP23 |
DSE7320 is an advanced control module based on micro-processor, containing all necessary functions for protection of the genset and the breaker control. It can monitor the mains supply, breaker control and automatically start the engine when the mains are abnormal. Accurately measure various operational parameters and display all values and alarms information on the LCD. In addition, the control module can automatically shut down the engine and indicate the engine failure.
FDK silent Cummins 540 kw generator is designed by professional acoustic engineers based on years of experience. Now we can make the noise of the generator less than 80-85dB(A) at 1m, or 70-75dB(A) at 7m, 60-65dB(A) at 15m.
Generator set
|
Alternator
|
Low environment Temp
|
ATS
|
|
|
|
|
Fuel system
|
Control system
|
Voltage
|
Synchronized system
|
|
|
|
|
Open
|
Soundproof Version
|
||
Overall Size:L×W×H (mm) | 3450×1620×1950 | Overall Size:L×W×H (mm) | 5000×1900×2250 |
Weight (kg) | 5100 | Weight (kg) | 5600 |
Frequency Range / RPM | |
---|---|
Engine Brand | |
Fuel Type | |
Power Output (Standby Power) | |
Application |